Service Update

Due to scheduled maintenance, our online services will be temporarily unavailable on April 3, 2024 from 5:30 pm to 10 pm. We apologize for any inconvenience.  

Service Update

Due to scheduled maintenance, our online services will be temporarily unavailable on April 3, 2024 from 5:30 pm to 10 pm. We apologize for any inconvenience.  

Minimum Requirements for Upgrading of Electrical Systems

Information Bulletin

Information Bulletin: Minimum Requirements for Upgrading of Electrical Systems

May 19, 2010

Information Bulletin
Electrical

Reference Number:

B-E3 091214 2

Revision Number:

Rev 2



PART A: Service, Main Panel or Feeder Repair

  • All electrical work must be done under a valid electrical permit by a licensed contractor or a homeowner where allowed under Section 17 of the Electrical Safety Regulation.
  • Where a panel, main breaker or switch is repaired or replaced with one of the same amperage rating, the existing panel and conduit locations will normally be acceptable. Service grounding and bonding must be in good repair
  • It is the responsibility of the permit holder to ensure that all the circuits to be reconnected comply with rules 2-200 and 2-300 of the BC Electrical Code. Existing branch circuits which are adequate for the purpose may be reconnected without alteration.
  • FSR’s must comply with the Safety Standards General Regulation, Section 26 (2) and notify Technical Safety BC before, or at the time of final inspection:
    a. If unacceptable conditions for which they are not responsible remain; or
    b. If they have been asked to perform work which may leave a portion of an installation in an unacceptable condition.

If either of the conditions in “a” or “b” exist, the Safety Officer will advise the owner and issue an order for corrections that must be completed within a reasonable time.

 

PART B: Service, Main Panel or Feeder Upgrade

  1. All electrical work must be done under a valid electrical permit by a licensed contractor or a homeowner where permitted under Section 17 of the Electrical Safety Regulation.
  2. It is the permit holder's responsibility to ensure that all the circuits to be reconnected comply with rules 2-200 and 2-300 of the BC Electrical Code.
  3. FSR’s must comply with the Safety Standards General Regulation, Section 26 (2) and notify Technical Safety BC before, or at the time of final inspection:
    a. If unacceptable conditions for which they are not responsible remain; or
    b. If they have been asked to perform work which may leave a portion of an installation in an unacceptable condition.

If either of the conditions in “a” or “b” exist, the Safety Officer will advise the owner and issue an order for corrections that must be completed within a reasonable time.

  1. When the occupancy classification of a building is changed, the electrical installation must meet the requirements for the new occupancy classification.
  2. When a building or installation is completely rewired or upgraded, all wiring must comply with the requirements of the current Regulations and BC Electrical Code.
  3. When a building is partly rewired, upgraded or modified the following shall apply:
    a. Additions to existing branch circuits must comply with the requirements of the BC Electrical Code.
    b. Existing branch circuits which are adequate for the purpose may be reconnected without alteration subject to Rules 2-200 & 2-300 of the BC Electrical Code.
    c. Grounding & bonding must meet the current requirements of the BC Electrical Code.
  4. Overhead line clearance must comply with Rule 6-112 of the BC Electrical Code.
  5. Plug fuses, if used, are of a type that are non-interchangeable with fuses of a higher rating in accordance with Rule 14-204.
  6. All outlet boxes and receptacles are bonded to ground in accordance with Section 10 or protected with GFCI in accordance with Rule 26-702 2)
  7. Receptacles rated at 15 amperes are on circuits having overcurrent protection set at not more than 15 amperes in accordance with Rule 14-600.
  8. Existing exterior receptacles are GFCI protected in accordance with Rules 26-704 2) and 70-122 (4).
  9. Existing bathroom and washroom receptacles must be GFCI protected in accordance with Rule 26-704 (1).
  10. Circuits which have additional receptacles added in a dwelling sleeping area shall be AFCI protected.
  11. Switches in bathrooms are in accordance with Rule 30-320 (3)
  12. Electrical heating equipment in bathrooms must conform to Section 62.
  13. Dryer circuits are supplied with an approved receptacle in accordance with Rule 26-744 (3);
  14. Range circuits are supplied with an approved receptacle in accordance with Rule 26-744 (4 & 6); and
  1. It is recommended that owners consult with the local Building Authority regarding requirements for smoke alarms and carbon monoxide alarms.
 

PART C: Reconnection of Existing Buildings or Installations

  1. A building or installation which has been disconnected may be reconnected without modification providing that:
    a. The occupancy has not changed; and
    b. The existing circuitry is in accordance with rules 2-200 and 2-300; and is adequate for the intended purpose.
    c. Service grounding and bonding is in good repair, Rule 2-300
    d. Overhead line clearances comply with Rule 6-112 of the BC Electrical Code.

Provincial Safety Manager - Electrical

References:

Bill 19 – 2003 Safety Standards Act
BC Reg. 100/2004 Electrical Safety Regulation
BC Reg. 105/2004 Safety Standards General Regulation
BC Reg. 186/2009 B.C. Electrical Code

Attachment
Size
117.77 KB